1. Features and Characteristics
Optional Features
2. Operating Modes
ICON operates in of the six modes described below.
Operating modes can be selected from the front keypad. Proper messages are displayed on LCD & led in each of the modes.
These six modes are:-
1. Auto---- to be selected from front key pad
2. Manual ---- to be selected from front key pad
3. Test ----- to be selected from front key pad
4. Bypass ----- (Not from the Front keypad)
5. Mains Display ----- (Not from the Front keypad)
6. Programming---- to be selected from front key pad
2.1 Auto Mode
In the auto mode of operation, GENSET is started automatically, if the mains either fail or exceed operating limits , the mains CB is opened and generator CB is closed.
2.1.1 Auto Stand by Mode: In Normal condition the controller remains in this mode. Voltages of the three phases are monitored continuously for operating limits . Operating limits are specified by UV / OV , phase connection error or phase missing. If any of these operating limits are exceeded then ICON takes following action:
2.1.2 Auto start Mode: The Genset Start process is initiated.
Start Delay : During engine start delay it waits to see if mains has returned to normal operating limits . This avoids false tripping .
Preheater : Optional . Starts supply to the preheater coil.
Fuel Solenoid On : After a delay the fuel Solenoid relay is energised with 2 options.
Cranking : After engine start delay is over , crank relay operates. Min Cranking time is 2 sec & max time is 4 sec. If Oil Pressure & Speed develops above specified threshold limits , bet 2 and 4 secs the crank relay is made OFF. The threshold limits for Oil P is warning limit set through programming & the threshold limit for speed is 1000 rpm
If the Oil P & Speed are not developed above specified limits another crank is attempted after a delay of 6 seconds. The process continues till the threshold limits are reached. If the Oil P & speed is still not reached after certain no of Crank attempts ( as programmed ) “Start Fail” is declared.
If the cranking is successful the Genset checking process starts.
Genset Checking : A delay is provided to check the following parameters .
Engine Speed : within Underspeed & Overspeed trip limits
Genset Voltage : within UV/OV trip Limits.
If above parameters are within limits then Genset is declared as STABLE. DG ON led ismade ON.
Mains Contactor OFF : After the Engine is found stable , the mains contactor is made OFF. Mains Contactor led gets OFF.
Genset Contactor ON : After programmable delay Genset Contactor is made ON.
LCD display starts displaying Genset parameters.
The Genset remains in this mode till ----- Mains is restored or any fault occurs.
2.1.3 Auto Normal Shut Down Mode:
When the Mains is restored, the Generator CB is opened and Mains CB is closed after the Mains restoration time. Then after a pre-programmed re-cooling time, the GENSET is shut down.
The Mains restoration time ensures that the Mains supply voltage is stable before it is made available to consumer load.
Genset CB closure is confirmed by checking that there is NO LOAD on Genset. If Genset CB non closure is sensed or Genset does not stop properly it goes to Fault Acknowledge Mode.
Otherwise at the End of this process the Controller goes back to 2.1.1 Auto Stand by Mode.
2.1.4 Auto Fault Shut Down Mode:
When the fault occurs the Generator CB is opened and Mains CB. The Controller goes to FAULT Acknowledge Mode with proper message on LCD Display as well as leds.
After acknowledging the fault ( correcting the fault ) it goes to Manual Mode & proper mode is to be selected at this time.
2.2 Manual Mode
2.2.1 Manual Stand by Mode
In this mode ICON ignores mains voltage. It only responds to Start and Stop commands from the keypad
Precaution: Before giving Start command to generator, one must ensure that the generator CB is open
2.2.2 Manual start Mode
Start key operation initiates the start operation.
The sequential process mentioned in the Auto Start is executed. This whole process can be made manual , if specified accordingly. If Manual Process is selected , after each STEP , Start key is required to be pressed as displayed on the LCD.
When Genset is ON, The generator CB may now be switched on from keypad provided that the Mains CB is off .
LCD display starts displaying Genset parameters.
The Genset remains in this mode till ----- STOP KEY pressed or any fault occurs
2.2.3 Manual Normal Shut Down Mode:
Stop key initiates this mode. The Controller follows all the steps automatically or manually (if specified ) as mentioned in the 2.1.3 Auto Normal Shut Down Mode.
Genset CB closure is confirmed by checking that there is NO LOAD on Genset. If Genset CB non closure is sensed or Genset does not stop properly it goes to Fault Acknowledge Mode.
If this process isexecuted successfully Controller goes to 2.2.1 Manual Stand by Mode.
2.2.4 Manual Fault Shut Down Mode:
When the fault occurs the Generator CB is opened and Mains CB. The Controller goes to FAULT Acknowledge Mode with proper message on LCD Display as well as leds.
After acknowledging the fault ( correcting the fault ) it goes to Manual Mode & proper mode is to be selected at this time.
2.3 Test Mode
Test Mode is selected by pressing the TEST key on the front pad, entering thepasswaord.Test Mode can be selected only in 2.1.1 Auto Stand by Mode & 2.2.1 Manual Stand by Mode. In this mode no-load and load test run of the GENSET is possible
If Test Mode is selected , it passes through all the STEPS mentioned in 2.1.2 Auto start Mode.
If the start process is executed successfully , Genset Parameters are displayed for at least 2 times before Shut down process starts ( the timing for test mode run can be specified ).
The Shut down process starts as mentioned in 2.1.3 Auto Normal Shut Down Mode:
If Fault is generated during the operation shut down process starts as mentioned in 2.1.4 Auto Fault Shut Down Mode:
If Mains failure is occurred during the test mode operation, the Mains emergency operation is initiated automatically.
At the end of successful completion of Test Mode the controller goes back to Previously selected mode.
2.4 By Pass mode
Bypass mode is selected by selecting proper digital input.
In the Bypass mode all the Genset Parameters are displayed and it keeps on displaying them unless and until the Bypass digital input is restored to normal position.
In Bypass mode the Controller has no control over the Generator operations. The Genset has to be Started / Stopped externally .
This mode cannot be selected from the front keypad
2.5 Mains Display Mode.
Mains Display Mode is selected from respective digital input .
In this mode all the parameters of the Mains are displayed and it keeps on displaying them unless and until the respective digital Input is restored to normal position.
This mode cannot be selected from the front keypad
2.6 Programming Mode
This mode basically helps in programming various parameters of the ICON3.There are various sub modes in this mode and they are: (All the following passwords are editable)
| Password 1111 | Set RTC - In this RTC mode we change RTC Date (dd/mm/yy) and Time (hh:mm:ss) |
| Password 2222 | In this mode we can view and edit all the factory settings. The parameters in this mode are as follows: Maintenance Due date (dd/mm/yy); Dispatch Date (dd/mm/yy) |
|
Password 3333 |
In this mode there are two options View and Change.In View mode we can view all the parameters which have been programmed but we cannot edit them. In the Change mode we can edit all the parameters and then save as per the user requires. The parameters in this mode are as follows: Baud Rate;BatteryVoltage;Digital I/p and O/p Polarity;Phase;Mains OV trip & warning value;Mains UV trip & warning value;Genset OV trip & warning value;Genset UV trip & warning value;Over Speed (RPM) trip & warning value;Under Speed (RPM) trip & warning value;Genset Overload to trip & warning value;Genset No Load trip & warning value;Oil Pressure (trip & warning value);Oil Temperature (trip & warning value);Coolant Temperature (trip & warning value);Canopy Temperature (trip & warning value);Fuel Low Level threshold;Crank Counter;Digital I/P Signal (enable/disable);(canopy temp, low oil pressure, V belt, low radiator water level, overspeed, under speed, remote start, remote stop and digital i/p 11,12,13,14,15,16);Start/Stop delay Timer;Preheat Timer;Safety on Timer;Warm up/Cool down Timer;Crank On/Off Timer;Contact delay Timer;Engine off Timer;Alternator trip & warning value;Analog I/P Signal (enable/disable);(Oil pressure, oil temp, cool temp, canopy temp, alt temp and Genset rpm);Action type --- Energise to On/ Energise to OFF.;CT Ratio;Mobile number1 and number 2;Alarm time; Total runtime;Genset Rating;BTS Low limit;AC temp (on/off) |
|
Password 4444 |
In this mode we can basically calibrate the following parameters:
In this mode we can basically calibrate the following parameters
|